Product

Non-Pressurized Condensed
Aerosol Generators

JIL-E1000 / JIL-TH1000 / JIL-E/TH1000

JIL-E1000

JIL-E1000

Electrical Parameter
Activating voltage:
DC3∼24/AC3-220V
Min activating current:
≧250mA/5mS
Max safety current:
≦150mA/5min
JIL-TH1000

JIL-TH1000

Thermal Parameter
Activation Temperature
(Other Temperature upon request)
57°C Orange
68°C Red
79°C Yellow
93°C Green
141°C Blue
JIL-E/TH1000

JIL-E/TH1000

Hybrid Parameter
(Electrical + Thermal)
Parameter of electrical Activator
Activating voltage: DC3∼24/AC3-220V
Min activating current: ≧250mA/5mS
Max safety current: ≦150mA/5min
Thermal Activator Thermal Cord Activator Activation Temperature
175°C
300°C
Glass Bulb Activator Activation Temperature
(Other Temperatures upon request)
57°C
68°C
79°C
93°C
141°C

FEATURES:

  • Zero Global Warming Potential
  • Zero Atmospheric Life
  • Zero Ozone DepletionPotential
  • Non-toxic
  • A simple and Effective fire suppression system

Technical Specification

Description Electrical Thermal Hybrid
Modal 1000g 1000g 1000g
Dimension ∅168*195mm (other sizes upon request) ∅168*195mm (other sizes upon request) ∅168*195mm (other sizes upon request)
Total weight 6.5kg 6.5kg 6.5kg
Compound weight 1000g 1000g 1000g
Volume coverage 10m3 10m3 10m3
Discharge time 18 sec 18 sec 18 sec
Activation Electrical Activation Thermal Activation Electrical / Thermal Activation
Operating condition -50°C - + 90°C/Up to 95%RH -50°C - + 90°C/Up to 95%RH -50°C - + 90°C/Up to 95%RH
Color Original color of SUS304 stainless steel Original color of SUS304 stainless steel Original color of SUS304 stainless steel
Spout temperature ≦200°C(5mm from the outlet) ≦200°C(5mm from the outlet) ≦200°C(5mm from the outlet)
The safe distance from the spout for person 1.5m 1.5m 1.5m
Use life (Life-span) 10 years more 10 years more 10 years more
Class Fire A, B, C, F A, B, C, F A, B, C, F
CE approval Related to CE Directive(s):2014/35/EU (Low Voltage) Related to CE Directive(s):2014/35/EU (Low Voltage) Related to CE Directive(s):2014/35/EU (Low Voltage)
CE standard CEN/TR 15276-1:2009 CEN/TR 15276-1:2009 CEN/TR 15276-1:2009